Customization: | Available |
---|---|
Application: | Construction, Industrial, Power Station |
Voltage: | Low and Medium Voltage Cable |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Medium Voltage Xlpe Cable 6kv 10kv 35kv Mv Power Cable
|
Product Overview |
Item | Construction | |
Conductor | Annealed copper | |
Insulated | XLPE | |
Shielding | Semi-conductive tape | |
Metal shieding | Copper tape | |
Jacket | PVC | |
Rated voltage | 8.7/15KV | |
Conductor Size | 3X120mm2 | |
Color | Black |
Direction for use XLPE polyethylene insulated power cables, This product is applicable to being fixedly laid on the transmission and distribution line of alternative current rating 50Hz and rated voltage up to 8.7/15 kV with the use for power transmission, which is applied to the range of distribution network, industrial equipments, high electricity consumption places etc. |
Operating characteristics
1. Rated Voltage Rated Voltage of cable U0/U(Um),as follow: U0/U(Um)=8.7/15(17.5)kV. 2. The rated temperature of conductor The maximum long-time working temperature of the cable conductor is 90ºC. During having a short circuit, lasting less than 5 seconds, the maximum temperature of the cable conductor shall not be above 250ºC. 3. Ambient temperature for laying The ambient temperature for laying shall be above 0ºC, otherwise the cable need be preheated. 4. The bend radius The minimum bend radius of the cable see the table 2 Medium Voltage power cable Table 2 The minimum bend radius of the cable |
Item | Three -core | |
Unarmored | Armored | |
Minimum bend radius of the cable in course of installation. | 15D | 12D |
The minimum bend radius of the cable close to the junction box and terminal | 12D | 10D |
Note: D is outer diameter of the cable |